June 2016
Hotfix_57433_56045_56976_VIP

This Hotfix includes fixes for the following:
1. SCR 57433 - the VIP Data Monitor module events are processd incorrectly. Both ON and OFF transitions generate independent alarms visible in the Active Alarms page in the Alarms web application. The hotfix reverts the VIP Data monitor module back to pre-PME8 behaviour, i.e. the Data Monitor module transitions are not treated like alarms, but rather as simple events.
2. SCR 56045 - The VIP Database Import module will time out on queries that take longer than 30 seconds. The hotifx VIP uses the IONConnectionTimeout registry setting to set the timeout (60 seconds by default)
3. SCR 56976 - The VIP would interpret large 16 bit values coming from an OPC client incorrectly.


To deploy:
1. Shut down all WinPM.Net VIP windows services
2. Rename the existing vip.exe in the \system\bin directory.
3. Copy in the updated version of vip.exe
4. Restart the WinPM.Net VIP services