HEAT LOSSES FOR METAL-CLAD SWITCHGEAR SERIES 5
To document heat losses for Series 5 MASTERCLAD Metal-Clad Switchgear. 5-15kV, 50/63 kA
2. APPLICABLE TO
3. PROCEDURE
3.1. Heat Loss/Heat Rise Tests
The heat losses listed below were measured during the switchgear heat rise tests. These maximum losses would apply if each breaker and breaker bussing and the main busses were loaded 100% of the time. If the actual load is not known, the listed 80% load would be a conservative value to use.
|
DESCRIPTION |
100% LOAD |
80% LOAD |
|
1200A Breaker |
990 Watts |
790 Watts |
|
2000A Breaker |
1600 Watts |
1280 Watts |
|
3000A Breaker |
2300 Watts |
1840 Watts |
|
1200A Main Bus per Bay |
180 Watts |
140 Watts |
|
2000A Main Bus per Bay |
460 Watts |
370 Watts |
|
3000A Main Bus per Bay |
720 Watts |
570 Watts |
3.2. Heat Loss/CT Rating
A more accurate heat loss can be obtained by using 80% of the CT rating of each breaker as the maximum load. A safety factor should be added if the load may be increased in the future. The losses listed below are pro-rated from the maximum breaker heat losses.
|
CT RATIO |
100% LOAD |
80% LOAD |
|
400/5A |
330 Watts |
260 Watts |
|
600/5A |
500 Watts |
400 Watts |
|
800/5A |
660 Watts |
520 Watts |
|
1000/5A |
830 Watts |
660 Watts |
|
1200/5A |
990 Watts |
790 Watts |
|
1500/5A |
1200 Watts |
960 Watts |
|
2000/5A |
1600 Watts |
1280 Watts |
|
2500/5A |
1900 Watts |
1520 Watts |
|
3000/5A |
2300 Watts |
1840 Watts |
The “main bus per bay” losses have to be added to these breaker losses.
If units are equipped with space heaters, add 400 watts per bay.
|