Version:
========
System Package UPS 18.0

System Package filename: SRYL1225UPS_18-0.enc

Includes:

Battery Module firmware version:         8.49
Intelligence Module firmware 1 version:  IMA 10.0
Intelligence Module firmware 2 version:  UPS 18.0
Power Module Firmware version:           PMA 05.0
External Battery Frame Firmware version: XRC 01.1

Applicable Models:
==================

Not all models included.

SRYL4K13XLM24, 	SRYL4K18XLM24, 	SRYL4K13RMXLM, 	SRYL4K18RMXLM,
SRYL5K15XLT18, 	SRYL5K20XLT18, 	SRYL5K15XLT24, 	SRYL5K20XLT24, 
SRYL5K15RMXLT, 	SRYL5K20RMXLT, 	SRYL9K13XLM24, 	SRYL9K18XLM24, 
SRYL9K13RMXLM, 	SRYL9K18RMXLM, 	SRYL10K15XLT18,	SRYL10K20XLT18, 
SRYL10K15XLT24,	SRYL10K20XLT24,	SRYL10K15RMXLT,	SRYL10K20RMXLT,
SRYL13K13XLM24, SRYL13K18XLM24, SRYL13K13RMXLM, SRYL13K18RMXLM,
SRYL15K15XLT18, SRYL15K20XLT18, SRYL15K15XLT24, SRYL15K20XLT24, 
SRYL15K15RMXLT, SRYL15K20RMXLT, SRYL18K18RMXLM, SRYL18K18XLM24,
SRYL20K20RMXLT, SRYL20K20XLT18, SRYL20K20XLT24

Compatibility:
==============	
UPS Networking Management Card 3 (NMC3) firmware v2.5.1 for Smart-UPS Ultra (2.5.1.3) or later

Upgrade AP964X Network Management Card (NMC) and NMC Display to latest firmware version
before proceeding with UPS firmware upgrade

Upgrade Requirements:
=========================

Existing firmware of UPS 10.8 or higher.

Upgrade Instructions:
====================	
How to Install the Smart-UPS Modular Ultra NMC/Display Firmware using the USB Port
Web link - https://www.se.com/us/en/faqs/FAQ000261841/

How to Install Smart-UPS Modular Ultra Firmware Using the Display and USB Port
Web Link - https://www.se.com/ie/en/faqs/FAQ000261838/

How do I update my Smart-UPS firmware using the web interface of my Network Management Card?
Web Link - https://www.se.com/ca/en/faqs/FA170679/

Users manual - See link on product web page

Release Notes (UPS 18.0):
=========================

 Features - N/A

 Improvements

  1. Reduce occurrence of "UI I2C communications alarm detected [1421-00XX]" and related alarms during startup.
  
 Known Issues

  1. Auto-update of a new IM fails if an extra NMC is installed in the SmartSlot


Release Notes (UPS 17.0):
=========================

 Features - N/A

 Improvements

  1. Improve phase control of 120/208 configuration to prevent low voltage on 208V output.
  2. Improved bypass acceptable range for 100/200 setting.
  3. Improved firmware upgrade behavior.

 Known Issues

  1. Auto-update of a new IM fails if an extra NMC is installed in the SmartSlot


Release Notes (UPS 16.0):
=========================

 Features - N/A

 Improvements

  1. Battery firmware (8.49) - ensure proper power off operation
  2. Battery firmware (8.49) - prevent premature reduction in battery state of health
  3. Battery firmware (8.49) - Reduce likelihood that that system will report new battery as not being present

 Known Issues

  1. Auto-update of a new IM fails if an extra NMC is installed in the SmartSlot
  2. Auto-update of a new IM is not always successful.  Error code 1504.
  2. 208V output voltage randomly drops below specified limits.  120V outputs are unaffected.  120/240 and 100/200 settings are unaffected.
  3. Bypass acceptable range for 100/200 and 120/208 setting are the same when they should be different.
  4. System may not accept firmware upgrade if the system has been operating for a long period of time.
  5. RIM may not get properly updated after firmware upgrade.  Need to upgrade RIM separately.


Release Notes (UPS 15.0):
=========================

 Features
 
  1. Added detection and reporting of IM versus PM measurement discrepancies
  2. Provide SBU (SRYLSBP20KP) status information (requires latest NMC Display firmware for correct messages)
  3. Added capability to upgrade UPS firmware to future versions when UPS output is on

 Improvements

  1. Improve compatibility with inductive (transformer) loads
  2. Improve detection of bypass relay position
  3. Reduce Battery not compatible warnings
  4. Reduce RS-232 comm alarms
  5. No longer set battery module status on NMC GUI as warning when battery module firmware will be updated
  6. Self test will no longer be refused when the number of battery modules is less than the number of
     power modules.  Other conditions still apply.
  7. Improve display behavior when SBU signal cable is installed or removed
  8. Reduced delay in logging specific events
  9. Allow system to complete self test even if it is disabled by user before self test completion
 10. Improve battery over discharge protection
 11. Improve firmware upgrade process
 12. Improve alarm clearing function
 13. Improve power module response to bad battery
 14. Improve module presence detection
 15. Improve certain alarm detection behavior
 16. Improve log messages
 17. Improve accuracy of reported run time when powering unique loads
 18. Improve accuracy of reported run time when low capacity battery module is installed
 19. Improve accuracy of reported run time with low output load or large number of batteries
 20. Improve initialization messages when intelligence modules have different firmware

 Known issues

  1. Auto-update of a new IM fails if an extra NMC is installed in the smart slot

 Note:  UPS 15.0 was only released to field service representatives.

 Release Notes (UPS 13.3):
=========================

 Features - N/A

 Improvements

  1. Eliminated potential that the system would get stuck indicating "Graceful Shutdown
     shutdown in progress" if the Main Intelligence Module (MIM) is removed during a "Reboot
     UPS" process
  2. Eliminated potential that the system would momentarily turn off the output if the MIM is
     removed immediately after a "Reboot UPS" process is completed.

 Known Issues

  1. High inductive/transformer load can cause DC bus error during start up or transfer to battery
  2. Installing a discharged battery will cause reported run time to be low even if other 
     batteries are fully charged
  3. Auto-update of a new IM fails if an extra NMC is installed in the smartslot

Release Notes (UPS 13.2):
=========================

 Features
 
  1. Support for Firmware update when the UPS is in Manual Bypass state
  2. Ability to Auto-upgrade new module (intelligence, power) FW if they do not match the
     system firmware (see Module Compatibility)
  4. Warning when Redundant Intelligence Module (RIM) is starting up and not ready to take control
     of the system
  5. Alarms for no PMs present, incorrect firmware, and other internal errors 
  6. Support for 100/200V Output Voltage setting
  7. Support for Low Runtime Warning Setting
  8. Support for High Apparent Power Warning Setting

 Improvements

  1. Eliminated false log entries for SPI communication alarm detected \ cleared
  2. Eliminated false log entries for XR frame disconnected \ Extended run frame detected
  3. System will properly show 100% battery capacity when batteries are fully charged
  4. Removed alarm when the number of battery modules is less than the number of power modules
     Alarm will only occur if battery modules cannot suport the load (~5kW per battery)
  5. Updated alarm reporting
  6. Updated warning reporting
  7. Eliminated false log entries for low run time
  8. Improved reported run time accuracy at end of discharge
  9. Improved efficiency calculation and reporting
 10. Added log events for turn on/turn off commands
 11. Corrected certain bypass behavior
 12. Improved consistency of overload behavior while in bypass
 13. One Line diagram battery LED behavior changed to turn RED when batteries cannot support the load
 14. Eliminate situations where battery charging would incorrectly stop
 15. System no longer turns output back on automatically when doing a power cycle using the system enable switch while AC input is present

 Known Issues

  1. High inductive/transformer load can cause DC bus error during start up or transfer to battery
  2. Installing a discharged battery will cause reported run time to be low even if other batteries are fully charged
  3. Auto-update of a new IM fails if an extra NMC is installed in the smartslot

Module Compatibility:
========================

Compatible with Power Module (PM) firmware PMA 5.0

 What to expect when installing a PM with PMA 1.3 (included in system package UPS 10.8):
  If the UPS output is ON,
    the PM will automatically connect to the output (solid green LED).
  If the UPS output is OFF,
    the PM will stay disconnected from the output (pulsing green LED).
  After 5 minutes, the system will display a warning (Unknown UPS internal error [1511-00XX]).
  The warning means the PM firmware is not the same as the version included in the system package.
  If the output is ON,
    the PM will NOT auto update!
  If the output is OFF,
    the PM will auto update to PMA 3.3 in 2 minutes and the warning will clear.

 What to expect when installing a PM with PMA 3.3 (included in system package UPS 13.2/UPS 13.3):
  If the UPS output is ON,
    the PM will stay disconnected from the output (pulsing green LED)).
  If the UPS output is OFF,
    the PM will stay disconnected from the output (pulsing green LED)).
  After 5 minutes, the system will display a warning (Unknown UPS internal error [1511-00XX]).
  The warning means the PM firmware is not the same as the version included in the system package.
  The PM will auto update to PMA 3.3 in 2 minutes and the warning will clear.
  If the UPS output is ON after the auto update is complete,
    the power module will connect to the output (solid green LED).

Compatible with Intelligence Module (IM) firmware UPS 18.0 / IMA 10.0

 What to expect when installing an IM with UPS 10.8 FW in the empty IM slot:
  If the output is OFF,
    After 15 minutes, the system will display a warning (Unknown UPS internal error [1502-00XX]).
    The warning means the new IM firmware is not same as the firmware of the IM in control.
  If the output is ON,
    the system will display no warning message.
  The new IM will NOT auto-update to UPS 13.2.
  To get the new IM to the latest firmware, the UPS firmware upgrade process must be performed
  with the UPS 10.8 IM acting as MIM.

 What to expect when installing an IM with UPS 13.2 or later in the empty IM slot:
  After 15 minutes, the system will display a warning (Unknown UPS internal error [1502-00XX]).
  The warning means the new IM firmware is not the same as the firmware of the IM in control.
  The new IM will auto update to UPS 18.0 firmware in ~1 hour and the warning will clear.
  A failure to auto update results in a warning (Unknown UPS internal error [1504-00XX]).
  In the event of an auto update failure, to get the new IM to the latest firmware, the UPS firmware
  upgrade process must be performed while the IM with older firmware is acting MIM (preferably
  alone in the system with output off).

Compatible with Battery Module (BM) firmware 8.49

  If a BM with firmware other than 8.49 is installed, the main intelligence module will update
  the BM firmware to 8.49.
  There is no notification that there is mismatched firmware.
  Battery module FW update is done in the background and can take several hours to complete.